strutture:lnf:da:btf:dispositivi:btf_timing
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| strutture:lnf:da:btf:dispositivi:btf_timing [2012/11/28 18:23] – foggetta@infn.it | strutture:lnf:da:btf:dispositivi:btf_timing [2024/03/19 16:02] (current) – [Additional Triggers] diociaiu@infn.it | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| + | ======TIMING====== | ||
| + | **Service to the user** | ||
| + | The user have a 2-channel arbitrary delay generator system {{: | ||
| + | remotely controlled in BTF control room with the respecive bypass in BTF Hall. | ||
| + | User customizable trigger signal (source LINAC SYS) | ||
| + | **{{: | ||
| + | |||
| + | __BTF Setup Menu (**BSM**)__\\ | ||
| + | -> **Go Forever** = lets the DAFNE injection rejected pulses (till the Odoscope one) to be delivered at set frequency to BTF\\ | ||
| + | -> **Single Shot** = only one pulse delivered to BTF, after the DAFNE injection pulses\\ | ||
| + | \\ | ||
| + | __General Timing Status (**GTS**)__\\ | ||
| + | -> **Normal** = cutoff trigger signal @ BTF (the DHPTB101 still works!!!)\\ | ||
| + | -> **BTF** = gives trigger signal @ BTF and implements BTF status setup (**BSM**)\\ | ||
| + | -> **BTF one shot** = gives trigger signal @ BTF and implements BTF status setup for one shot per second or manual shot\\ | ||
| + | \\ | ||
| + | __ODOSCOPE setup (**ODO**)__\\ | ||
| + | -> **DAFNE** = cutoff the DHPTB101 \\ | ||
| + | -> **DAFNE+BTF** = permits DHPTB101 to pulse\\ | ||
| + | \\ | ||
| + | \\ | ||
| + | |||
| + | **__DAFNE+BTF status__**\\ | ||
| + | \\ | ||
| + | **MANUAL SHOT**\\ | ||
| + | **GTS** -> BTF 1 shot\\ | ||
| + | **BSM** -> Single shot\\ | ||
| + | **ODO** -> DAFNE + BTF\\ | ||
| + | Press RUN BTF button and it fires one pulse\\ | ||
| + | \\ | ||
| + | **One shot per second**\\ | ||
| + | **GTS** -> BTF 1 shot\\ | ||
| + | **BSM** -> Go Forever and number of impulses = 1\\ | ||
| + | **ODO** -> DAFNE + BTF\\ | ||
| + | Press RUN BTF button and it fires at 1 Hz (two pulses per second in DAFNE injection)\\ | ||
| + | \\ | ||
| + | ** Maximun shot rate**\\ | ||
| + | **GTS** -> BTF\\ | ||
| + | **BSM** -> Go forever and number of impluses = 49\\ | ||
| + | **ODO** -> DAFNE + BTF\\ | ||
| + | \\ | ||
| + | |||
| + | ==== BTF Signals ==== | ||
| + | |||
| + | **Q4 signal || BTF word signal** => Syncro word (~8usec before gun pulse) | ||
| + | Cable panel n.11(inside) SlowControl rack's hall in the BTF Control Room -> output from trg board send to 11(inside)-1 | ||
| + | \\ | ||
| + | **BTFTG1**// | ||
| + | Cable panel n.11 in BTF Control Room (near BTF Hall concrete wall) -> output from 11-1, delayed by Stanford C && !D, send to 11-3, from 11(inside)-3 send to a cable TG1BTF in BTF Hall | ||
| + | \\ | ||
| + | **BTFTG2**// | ||
| + | Cable panel n.11 in BTF Control Room (near BTF Hall concrete wall) -> output from 11-1, delayed by Stanford A && !B, send to 11-2, from 11(inside)-2 send to a cable TG2BTF in BTF Hall | ||
| + | \\ | ||
| + | **BTFTG0 A/B**//(btf staff)// signal => output from trg board, delayed by Stanford C && !D, send to a cable TG0BTF in BTF Hall | ||
| + | **BTFTG0 C/D**//(btf staff)// signal => output from trg board, delayed by Stanford C && !D, send to a cable TG0BTF in BTF Hall | ||
| + | \\ | ||
| + | |||
| + | ==Stanford BTF Setup== | ||
| + | ** TRG EXT Setup **\\ | ||
| + | THreshold = -0.5V\\ | ||
| + | Slope = Negative\\ | ||
| + | Trigger Term = 50Ohm\\ | ||
| + | \\ | ||
| + | ** GPIB addr **\\ | ||
| + | User = 14\\ | ||
| + | \\ | ||
| + | \\ | ||
| + | \\ | ||
| + | A = 15.79 usec\\ | ||
| + | B = A + 200 nsec (as gate)\\ | ||
| + | C = 15.79 usec\\ | ||
| + | D = C + 200 nsec (as gate)\\ | ||
| + | \\ | ||
| + | **BTFDAQ Timing Unit**\\ | ||
| + | DAQ Delay ~200nsec\\ | ||
| + | \\ | ||
| + | |||
| + | |||
| + | ==== Additional Triggers ==== | ||
| + | |||
| + | There are additional triggers available for the users: | ||
| + | |||
| + | ** BTF && | ||
| + | it is possible to select an electron/ | ||
| + | This trigger starts 60 ns after the LINAC trigger.\\ | ||
| + | {{: | ||
| + | |||
| + | ** BTF && Calorimeter **\\ | ||
| + | it generates a TTL trigger signal only if there is a LINAC trigger AND a signal in the calorimeter (see the purple signal on the scope screen). This Trigger starts 450 ns after the LINAC trigger.\\ | ||
| + | {{: | ||